The National Electrical Code (NFPA 70) is the primary standard for electrical installation in the United States, covering safety requirements and installation practices.
Figure 1.1: Professional electrical installation project demonstrating proper techniques and project management practices
General Lighting Load: 3 VA per square foot
Small Appliance Circuits: 1500 VA each (minimum 2)
Laundry Circuit: 1500 VA (minimum 1)
Fastened-in-Place Appliances: Nameplate rating
Motors: Full load current × service factor
Heating/Cooling: Largest of the two
Demand Factor Application:
First 3000 VA at 100%
Remainder at 35%
Range loads at nameplate rating
Lighting: 3 VA per sq ft × demand factor
Receptacles: 180 VA per outlet × demand factor
Motor Loads: Full load amperes × voltage × 1.732
Fixed Appliances: Nameplate rating × demand factor
Typical Demand Factors:
Proper grounding and bonding are essential for electrical safety, system operation, and lightning protection.
Purpose: Provide a path for fault current and stabilize voltage
Fault Current Calculation:
$$I_f = \frac{V_{LL}}{\sqrt{3} \times Z_{total}}$$Where:
Purpose: Provide low-impedance path for fault current
EGC Sizing (250.122):
| Circuit OCPD (A) | EGC Size (AWG) |
|---|---|
| 15 | 14 AWG Cu |
| 20 | 12 AWG Cu |
| 30 | 10 AWG Cu |
| 40-60 | 8 AWG Cu |
| 100 | 6 AWG Cu |
| 200 | 4 AWG Cu |
| 300 | 2 AWG Cu |
Purpose: Dissipate fault current into earth
Electrode Sizing (250.52):
Purpose: Eliminate potential differences between metal parts
Enter load data to calculate electrical service requirements.
Test your understanding of Electrical Installation & Project Management with this comprehensive assessment.
Calculate the service load for a 2500 sq ft residence with 3 small appliance circuits, 1 laundry circuit, electric range (8000W), water heater (4500W), and 1 HP air handler motor.
Solution:
General Lighting: 2500 × 3 = 7500 VA
Small Appliances: 3 × 1500 = 4500 VA
Laundry: 1 × 1500 = 1500 VA
Fixed Appliances: 8000 + 4500 = 12500 VA
Motor: 1 HP = 745.7W (assume PF=0.8) ≈ 932 VA
Total Connected Load: 7500 + 4500 + 1500 + 12500 + 932 = 26932 VA
Apply Demand Factors:
First 3000 VA at 100% = 3000 VA
Remainder at 35% = (26932 - 3000) × 0.35 = 8376 VA
Service Load: 3000 + 8376 = 11376 VA
Service Size: 11376 / 240V = 47.4A → Use 60A service